Fog Hashing H200-S Hydro Cooling Rack

$16,890 (USD)

Fog Hashing H200-S Hydro Cooling Rack is designed for Antminer S19 Hyd, Antminer S21 Hyd, Antminer S23 Hyd and supports up to 36 units.

FogHashing H200 series is a Hydro Cooling equipment specifically designed for Bitcoin mining. Whether you are a professional miner or a beginner, Hydro Cooling Solution is the ideal choice to enhance mining efficiency.

This configuration includes the H200-S Rack, the CDU and the Dry Cooler.


Bulk purchase prices based on quantity:
10-29 30-49 50-99 100+
$16,046 $15,201 $14,357 $13,512

Shipping cost to your door is included in the price

  • Order dispatch within 48 hours
  • 30 days money-back buyer protection
  • FREE Worldwide DDP Shipping (0% Customs Taxes)
Guaranteed Safe Checkout

Fog Hashing H200-S Hydro Cooling Rack
Fog Hashing H200-S Hydro Cooling Rack
$16,890 (USD)
Please enable JavaScript in your browser to complete this form.
Subject of Inquiry

Fog Hashing H200-S Hydro Cooling Rack is designed for Antminer S19 Hyd, Antminer S21 Hyd, Antminer S23 Hyd and supports up to 36 units.

FogHashing H200 series is a Hydro Cooling equipment specifically designed for Bitcoin mining. Whether you are a professional miner or a beginner, Hydro Cooling Solution is the ideal choice to enhance mining efficiency.

Fog Hashing H200-S Hydro Cooling Rack Specifications:

H200-S RACK
Size1550mm(W)2200mm(H)400mm(D)
System Power Load (MAX)226kW
Miner Capacity36 * S19/S21/S23 Hydro
Input Voltage3-Phase 380V-415V, 50/60Hz
PDUPDC/PDU
Network1000M Network Switch*2
Operation Temperature-25 ~ 35℃
Operating Humidity5%~95%RH
Water ManifoldStainless Steel
HosePE/PTFE Hose + Quick Connects
H200-S CDU
Size800mm(W)2100mm(H)1000mm(D)
Cooling Capacity200kW
Power3.5kW
Input Voltage3-Phase 380V-480V, 50/60Hz
Cooling MediumPure water/Soften water+Antifreeze+Corrosion Inhibitor
Inlet/Outlet10°C (Normal)
14°C (High Performance)
Rated Flow Rate20m³/h
Operating Temperature-25℃~45℃
Operating Humidity5%~95%RH
PLC SystemConstant flow control with pressure regulation
Communication MethodModbus-RTU,TCP/IP
Design Pressure0.3MPa
H200-S Dry Cooler
ModelFHWDC200
ModuleDry Cooler V Type
Cooling Capacity200kW
Wight(Empty Load)800KG
FANs2
ConnectionDN50
FluidCoolant
Fluid flowrate20m³/h
Inlet/Outlet Temperature55℃/40℃
Ambient temperature35℃
Fin/Tube Materials304 Stainless steel,Al-mg/AI
Operating/Maximum Pressure0.3MPA/1.6MPA