Bitmain Antrack V2 Hydro – Antminer Hyd Cooling Mining Rack

$8,490 (USD)

The ANTRACK V2 is a cutting-edge mining unit designed to contain four ANTMINER S19/S21/S23 Hyd units, while optimizing the mining process using hydro-cooling technology.


Bulk purchase prices based on quantity:
10-29 30-49 50-99 100+
$8,066 $7,641 $7,217 $6,792

Shipping cost to your door is included in the price

  • Order dispatch within 48 hours
  • 30 days money-back buyer protection
  • FREE Worldwide DDP Shipping (0% Customs Taxes)
Guaranteed Safe Checkout

Bitmain Antrack V2 Hydro - Antminer Hyd Cooling Mining Rack
Bitmain Antrack V2 Hydro – Antminer Hyd Cooling Mining Rack
$8,490 (USD)
Please enable JavaScript in your browser to complete this form.
Subject of Inquiry

The ANTRACK V2 is a cutting-edge mining unit designed to contain four ANTMINER Hyd units or four ANTMINER U2 Hyd units or two ANTMINER U3 Hyd units, while optimizing the mining process using hydro-cooling technology. With a substantial capacity and a maximum power load of 24 kW, it efficiently meets the energy demands of cryptocurrency mining.

The ANTRACK unit is precisely constructed to enable speedy deployment and efficient heat recovery, representing a big step forward in the hydro-cooling mining experience.

Bitmain Antrack V2 Hydro Specifications:

1 – Mining Cabinet
Hardware Configuration
Size (Length*Width*Height), mm (without package)1200*600*1300
Size (Length*Width*Height), mm (with package)1460*1330*780
Net weight, kg (without package)130
Gross weight, kg (with package)185
Network connection modeRJ45 Ethernet 10/100M
Power Supply
Power supply AC Input voltage, Volt(1-1)380~415V AC
Power supply AC Input Frequency Range, Hz50~60
Power supply AC Input current, Amp(1-2)63

Water pump

Rated power, W450
Noise, dBA@1m60
Lift, m19
Size (Length*Width* Height), mm360*210*268
Plate heat exchanger
Maximum heat exchange power, kW30
Size (Length*Width* Height), mm305*106*64
Diameter of water pipe connector, mmDN20
2 – External Cooler
Hardware Configuration
Size (Length*Width*Height), mm (without package)1160*1035*1570
Size (Length*Width*Height), mm (with package)1310*1185*1770
Net weight, kg (without package)380
Gross weight, kg (with package)432
Power supply
Power supply AC input voltage, Volt(1-1)380~415V AC
Power supply AC input frequency range, Hz50~60
Maximum power supply AC input current, Amp(1-2)63
Heat pump
Heating Capacity (typical), kW32
Compressor Input (typical), kW8
EER (typical)3
Sound Level, Db(A)77
RefrigerantR134a
Heating water outlet temperature, °C80
Fan
Rated power, W1900
Noise, dBA@1m74
Size (Length*Height*Thickness), mm1010*1010*369
Water pump
Rated power, W370
Noise, dBA@1m74
Size (Length*Width* Height), mm328*205*461
Environment Requirements
Ambient temperature, °C-20~45
Water flow, L/min32.0~40.0 (Cabinet side)
Water pressure, bar≤3.5
Working fluid(1-4)Antifreeze (10%)
Installation distance, m(1-5)50
Liquid PH7.8~8.5
Storage temperature, °C-20~70
Operation humidity(non-condensing), RH10~90%

NOTE:

  1. Caution: Wrong input voltage may probably cause miner damaged.
  2. Three-phase AC input.
  3. The External cooler (heat pump) should be placed outdoors in a well-ventilated environment.
  4. If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
  5. The distance between mining cabinet and external cooler.